Ratings (VA/W ) |
10,000VA/ 10,000W |
Dimensions and Weight |
Dimensions (W×D×H) |
430 × 630 × 217 mm |
Unit Weight |
74.5kg |
Input AC Parameters |
Operating Frequency, Nom |
50 or 60 Hz (Factory default is 50 Hz ) |
Factory Default Voltage |
230 VAC |
Operating Voltage Range Without Battery Operation |
176 to 288 VAC (100 to 176 VAC with power derating) |
Maximum Allowable Voltage |
288 VAC |
Input Frequency Without Battery Operation |
40 to 70 Hz |
Output AC Parameters |
AC-AC Efficiency |
95% |
User-configurable Voltage |
200/208/220/230/240 VAC |
Factory Default Voltage |
230 VAC |
Frequency |
50 Hz or 60 Hz, Nominal |
Waveform |
Pure Sinewave |
Output Power Connection |
Output terminal block |
Main Mode Overload |
>150% minimum 200 ms, 125 – 150% for 60 seconds; 105 – 125% for 5 minutes; ≤ 105% continuous |
Internal Battery |
Charger Current |
2.25 A (default), maximum 8 A |
Type |
Valve-regulated, non-spillable, lead acid |
Qty x V x Rating |
2 x 8 x 12V x 9.0 AH |
Back-up Time at Full Load |
2 |
Back-up Time at Half Load |
7 |
Bypass Protection Limits |
Upper-limit Selections |
+ 10%, + 15%, + 20%; default + 10% |
Lower-limit Selections |
- 10%, - 15%, - 20%; default - 15% |
Disable-bypass Operation |
When the input frequency prevents synchronous operation |
General |
Operating Temperature, °C |
Full power up to 40 ºC (up to 50 ºC with derating) |
Storage Temperature, °C |
- 15 to + 40 |
Relative Humidity |
0 – 95% non-condensing |
Operating Elevation |
Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating |
Audible Noise |
<55 dBA |
Safety |
UL-1788 (Fifth Edition),C-UL listed, IEC 62040-1: 2017 Edition 2.0, EN 62040-1:2008+A1:2013 |
EMI/EMC/C-Tick EMC |
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A) CISPR22 Class A (RFI) |
ESD |
IEC/EN EN61000-4-2, Level 4, Criteria B |
Radiated Susceptibility |
IEC/EN EN61000-4-3, Level 3, Criteria A |
Electrical Fast Transient |
IEC/EN EN61000-4-4, Level 4, Criteria B |
Surge Immunity |
IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B |
Transportation |
ISTA Procedure 1E |