Model
|
OLS2000E
|
Capacity (VA/W)
|
2000VA / 1800W
|
Typology
|
Online (Double Conversion)
|
Energy-Saving Technology
|
Yes, ECO Mode Efficiency > 95%
|
Input
|
Voltage Range
|
120~139VAC for 0~25% Load
|
140~159VAC for 0~50% Load
|
160~179VAC for 0~75% Load
|
180~280VAC for 0~100% Load
|
Input Type
|
IEC C20
|
Frequency Range
|
40~70Hz
|
Output
|
UPS Outlets (Numbers)
|
(4) IEC C13 + Terminal Block
|
On Battery Output Voltage
|
Pure Sine Wave at 208, 220, 230, 240 Vac (Configurable)
|
On Battery Output Voltage Distortion (@Nominal Battery Voltage)
|
≤ 3% (Linear Load), ≤ 5%(Non-Linear Load)
|
On Battery Output Frequency
|
50 Hz / 60 Hz (Auto-Sensing or Configurable) ± 0.5%
|
Transfer Time (Typical)
|
0ms
|
Overload Protection
|
AC Mode: Warning only @ 110%>Load>105%, Transfer to bypass after 60sec @ 120%>Load>110%, Transfer to bypass immediately@ Load>120% Battery Mode: Warning only @ 110%>Load>105%,
Shutdown after 10sec @ 120%>Load>110%,
Shutdown immediately @ Load>120%
Bypass Mode: Warning only @ 130%>Load>105%, Shutdown immediately @ Load>130%
|
Surge Protection and Filtering
|
Surge Protection
|
Yes
|
DSL/Phone/Fax/Modem protection
|
RJ11/RJ45(One In/One Out)
|
Short Circuit Protection
|
UPS Output Cut off Immediately or Circuit Breaker Protection
|
Battery
|
Sealed Maintenance Free Lead Acid Battery
|
(6) 12V / 7AH
|
Configurable External Battery Pack (Max.)
|
3
|
Typical Recharge Time
|
5
|
Runtimes
|
Half load-Full load (mins)
|
16/6
|
Status Indication
|
Indicators
|
Power On, Line Mode, Battery Mode, Bypass Mode, ECO Mode,C/F Mode, Fault, Replace Battery
|
Audible Alarms
|
Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery
|
Communication
|
Power Management Software
|
PowerPanel® Business Edition
|
Management
|
Self-Test
|
Yes
|
Auto-Charge/Auto-Restart
|
Yes
|
Auto-Overload Recovery
|
Yes
|
Cold Start (DC Start)
|
Yes
|
Connectivity Ports
|
(1) Serial Port (RS232), (1) USB Port, (1) EPO/ROO
|
SNMP/HTTP Capable
|
Optional
|
Dimensions
|
337 x 196 x 416 mm
|
Weight
|